Inspection History Details
Permit: T05CM05272
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/25/2007 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :* LETTER OF TORQUE RECEIVED TODAY REVISION LETTER FOR SERVICE LATERAL CONDUCTORS AND FAULT CURRENTS RECEIVED TODAY |
|
| 07/16/2007 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION ONLY 1. INSTALL PANEL FEEDERS 2. INSTALL SERVICE CONDUCTORS 3. BOND SERVICE RACEWAYS AND ENCLOSURES 4. INSTALL SERVICE CONDUCTOR LUGS 5. PROVIDE TORQUE LETTER FOR EQUIPMENT 6. IDENTIFY SERVICE DISCONNECT 7. IDENTIFY ALL MAIN DISCONNECTS 8. METAL RACEWAY FOR GROUNDING ELECTRODE CONDUCTOR TO BE ELECTRICALLY CONTINUOUS. 9. INSTALL MAIN BONDING JUMPER BRACKET 10. INSTALL SERVICE FUSES 11. PROPERLY DERATE HOUSE PANEL BRANCH CKT'S 12. IDENTIFY PANEL DIRECTORY 13. BOND GAS PIPE 14. SPRINKLER BOND CLAMP TO BIG FOR PIPE HAVE EQUIPMENT OPEN FOR INSPECTION |