Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/22/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*GROUND W.H DISCONNECT MARK PANEL DIRECTORY FIX EMERGENCY BALLAST | |
| 01/30/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*NEED TO BOND SERVICE LATERAL RACEWAYS WITH PROPER SIZE WIRE ( SHELL SERVICE) PER NEC 250.66 NEED TO REMOVE GROUND TAP FROM PANEL A DISOCNNECT AND CT CAN ENCLOSURES AND INSTALL PANEL A EQUIPMENT GROUND TO NEUTRAL STEVE WILL MAKE THESE CORRECTIONS WITH TEP PRESENT. |