Permit: T05CM05262

Parcel: 10309018A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
02/22/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*GROUND W.H DISCONNECT MARK PANEL DIRECTORY FIX EMERGENCY BALLAST
01/30/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*NEED TO BOND SERVICE LATERAL RACEWAYS WITH PROPER SIZE WIRE ( SHELL SERVICE) PER NEC 250.66
NEED TO REMOVE GROUND TAP FROM PANEL A DISOCNNECT AND CT CAN ENCLOSURES AND INSTALL PANEL A EQUIPMENT GROUND TO NEUTRAL STEVE WILL MAKE THESE CORRECTIONS WITH TEP PRESENT.