Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/22/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 01/30/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* | |
| 01/26/2006 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The service is not per code.| 210* 1. NEED MINIMUM 1/0 CU GROUND TAP AND ROUTE DIRECTLY TO NEUTRAL LUG IN DISCONNECT 2. NEED MINIMUM 1/0 CU GROUND FROM NEUTRAL TERMINAL IN DISCONNECT TO C.T. CAN 3. INSTALL FUSES IN DISCONNECT 4. FINISH WIRING FOR SUB-PANEL 5. INSTALL ADDRESS ON SERVICE 6. SEAL UNDERGROUND RACEWAY |