Date Description Inspector Results Comments
01/20/2006 ELECTRIC - OUTDOOR LIGHTING Approved IVRS - Inspection :*
01/05/2006 ELECTRIC - OUTDOOR LIGHTING Partial Approval IVRS - Inspection :*INSTALL # 4 CU GROUND TAP TO SERVICE DISCONNECT NEC 250.66
INSTALL GROUNDING BUSHING ON RACEWAY GUTTER TO METER
INSTALL GROUNDING BUSHING ON RACEWAY METER TO DISCONNECT
INSALL CORRECT ADDRESS LABEL TO DISCONNECT
PROPERLY IDENTIFY PANEL DIRECTORY
GROUND W.H. DISCONNECT WITH # 10