Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - OUTDOOR LIGHTING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/20/2006 | ELECTRIC - OUTDOOR LIGHTING | Approved | IVRS - Inspection :* | |
| 01/05/2006 | ELECTRIC - OUTDOOR LIGHTING | Partial Approval | IVRS - Inspection :*INSTALL # 4 CU GROUND TAP TO SERVICE DISCONNECT NEC 250.66 INSTALL GROUNDING BUSHING ON RACEWAY GUTTER TO METER INSTALL GROUNDING BUSHING ON RACEWAY METER TO DISCONNECT INSALL CORRECT ADDRESS LABEL TO DISCONNECT PROPERLY IDENTIFY PANEL DIRECTORY GROUND W.H. DISCONNECT WITH # 10 |