Permit: T05CM05261

Parcel: 10511040D

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T05CM05261

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
01/20/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
12/30/2005 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*CORRECTIONS MADE
12/28/2005 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) LIGHT FIXTURES NEED TO BE SECURED TO GRID WITH LISTED CLIPS OR SCREWED TO GRID AT CORNERS
2) DON'T USE GRID SUPPORT WIRES FOR THE SUPPORT OF ELECTRICAL SYSTEM