Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/21/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 10/20/2005 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BOTTOM PLATE NORTH WALL MUST BE TREATED MATERIAL 2) NO WATER TEST DWV SYSTEM 3) PLAN CALLS FOR DEDICATED 20 AMP CIRCUIT TO GFCI 14-2 WIRED INSTALLED MUST BE 12-2 FOR GFCI 4) INSTALL AND ? UP EXHAUST FAN |
|
| 10/19/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) UNABLE TO LOCATE PLANS OR INSPECTION CARD ON SITE |