Permit: T05CM05246

Parcel: 117072670


Addresses:

745 S 3RD AV


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T05CM05246

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
12/18/2007 FRAMING Approved IVRS - Inspection :*
12/05/2007 FRAMING Partial Approval IVRS - Inspection :*
1) FINAL FRAME PENDING PLUMBING CHANGES, PLAN REVISIONS AND PLUMBING PROTECTION
2) OK TO INSULATE
12/04/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) HAVE LETTER ON TRUSSES AT ATTIC APPROVED BY DSD AND TRUSS ENGINEER
2) EXPOSE ROUGH PLUMBING DONE AT SHOWER AND TUB
3) PROTEC ALL PLUMBING CLOSER THAN 1 1/2" TO FACE OF STUDS
4) DUCT STILL RESTRICTED
5) REVISE DRAWING TO REFLECT REVISED PLUMBING
11/16/2007 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE ACCESS TO ATTIC
2) HAVE ARCHITECT OF RECORD JUSTIFY MAX LOAD ALLOWED ON BOTTOM CORD OF TRUSSES (BRACE TRUSSES PER SPECS)
3) GROUND ALL METAL BOXES
4) NO TEST ON DWV
5) VACUUM BREAKERS REQUIRED AT EXT. HOSE BIBS
6) NO TEST ON LINE
7) BLOCK 3 SIDES AIR DUCTS
8) CHECK FLEX DUCT, RETRICTED IN DINING ROOM PROTECT CONDENSATE LINE
9) PROPOSED REVISION TO INTERIOR PLUMBING SHALL BE REINSPECTED
09/28/2007 FRAMING Not ready for Inspection IVRS - Inspection :*