Permit: T05CM05213

Parcel: 115154990

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
08/16/2006 BUILDING - FINAL Approved IVRS - Inspection :*
08/11/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 6" CLEARANCE REQUIRED BETWEEN FURNACE FRONT AND CLOSED DOOR
2) KITCHEN MISSING CABINET AND RECEPTACLE NEXT TO FRIDGE
3) WALL MISSING BETWEEN DINING AND LIVING ROOM
4) MAX FUSE 30 AMP A/C DISCONNECT
5) A/C DISCONNECT CANNOT BE BEHIND UNIT
6) PAINT EXPOSED PLUMBING VENTS ON ROOF
8) KITCHEN GFCI CIRCUIT NOT TRIPPING AT RECEPTACLES
9) SUBMIT REVISED DRAWINGS REPLACING EVAP COOLER WITH A/C