Permit: T05CM05205

Parcel: 14027050D

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T05CM05205

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/28/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
05/08/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. YOU HAVE PIPING SUPPORTED BY OTHER PIPING. ALTHOUGH THIS IS NOT AN ACCEPTABLE PRACTICE I MAY ALLOW THIS IN SOME AREAS BUT, PROVIDE SEPARATE SUPPORTS FOR THE 2" MAIN WATER LINE, 1/2 COLD BRANCH LINE RESTING ON CEILING GRID, 3/4 HW BRANCH AND THE GAS LINE TO WATER HEATER.
2. THE REVISED PLANS ON SITE ARE NOT APPROVED.
3. THE REVISED PLAN DOES NOT APPEAR TO ADDRESS THE FIXTURES NOT INSTALLED PER YOUR ORIGINAL PLAN.
4. THE REVISED GAS DRAWING DOES NOT INCLUDE THE GAS BRANCH LINE RUNNING EAST-WEST IN THE SOUTHERN HALF OF BUILDING.
04/28/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
SEE NOTES FROM PREVIOUS INSPECTIONS.
OVERHEAD VENT ABOVE DF, HAND SINK AND LAVITORS REQUIRE SUPPORT AT EACH END. WATER PIPING NEED SUPPORT EVERY 6' AND GAS PIPING TO WH NEEDS SUPPORT.
PLAN SHOWS TWO SINKS P-6 THAT WERE NOT INSTALLED,
PLEASE REVISE TO SHOW DELETION OF P-6 SINKS.
GAS PIPING HAS BEEN MODIFIED, PLEASE PROVIDE A PIPING DRAWING. SEC OF GAS SYSTEM.
01/30/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REVISE PLAN TO SHOW WORK DONE, DELETE PLUMBING THAT WAS NOT DONE
2. SHOW CHANGES MADE ON GAS SYSTEM. SHOW ADDED FIXTURES. DF & SINK
3. PROVIDE PRESSURE TEST USING A GAUGE WITH 1/10 PSI INCREMENTATION
4. PROVIDE ACCESS TO ABOVE CEILING PIPING FOR INSPECTION.
5. PROVIDE HEAT TRAP NIPPLES ON WH TO MEET ENERGY CONSERVATION REQUIREMENTS
6. CORRECT DRIP AT WH - CORRECT COPPER PIPING TOUCHING FLUE. SEE PREVIOUS NOTES.
7. CAULK UNDERSIDE OF URINAL.
01/17/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
WATER HEATER VENT
WATER HEATER T & P AIR GAP
CLEAN OUT AT MOP SINK
CALL FOR INTERMEDIATE INSPECTION FOR ABOVE CEILING
COPPER UNDER 2" SHALL BE SUPPORTED AT 6' MAX
NO HUB VENTS SHALL BE SUPPORTED WITHIN 18" OF EACH JOINT.
PROVIDE TEST ON GAS SYSTEM - PROVIDE REVISED PRINT