Permit: T05CM05189

Parcel: 13824164B

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/06/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
APPROVED PER APPROVED PLANS
10/05/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
COMPLETE LIST FROM 9/28/06
SUPPORT FOR DRAIN PIPING TO FLOOR DRAIN
10/03/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
COMPLETE LIST FROM 9/28/06
LIST IS NOT COMPLETE
09/28/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- CALL FOR ABOVE CEILING INSPECTION
- PROVIDE BACKFLOW CERTS
- BACKFLOW PREVENTION DEVICES REQUIRED FOR NON-CARBONATED BEVERAGES.
- TERMINATE VENT ON EXTERIOR WALL.
- SUPPORT RP DRAIN AT CARBONATORS
- SECURE EXPANSION TANK, SECURE MOP SINK FAUCET
- PROVIDE 1 1/4" PIPING AT HW TO FIRST TEE.
- PROVIDE ACCESS TO ROOF
- ALL PLASTIC VENTS TO BE PROTECTED FROM UV RAYS
- CLEANOUT PLUGS SHALL HAVE A FACTORY TAP TO RECEIVE MACHINE SCREW.
- SEDIMENT TRAPS REQUIRED AT GAS EQUIPMENT.
- TRAP AND TRAP ARM SHALL BE THE SAME SIZE, TRAP ARM CANNOT INCREASE IN SIZE.
- INDIRECT WASTE PIPING REQUIRES CLEANOUTS AT CHANGE OF DIRECTIONS.
- ICE MAKER CONDENSATE SHALL DRAIN SEPARATE FROM
ICE BIN.
- AIR ADMITTANCE VALVE REQUIRES A LUVERED ACCESS TO ALLOW FREE FLOW OF AIR.
- AIR GAPS REQUIRED FOR INDIRECT DRAINS.

LIST MAY NOT BE COMPLETE.