Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/03/2006 | PLUMBING - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 05/08/2006 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* GAS PIPING ABOVE CEILING NOT COMPLETE. |
|
| 05/03/2006 | PLUMBING - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 04/28/2006 | PLUMBING - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 04/27/2006 | PLUMBING - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/26/2006 | PLUMBING - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 04/14/2006 | PLUMBING - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* THIS WORKMANSHIP IS NOT ACCEPTABLE NOTES FROM PREVIOUS INSPECTION HAVE NOT BEEN COMPLETED. ABS DWV IS REQUIRED TO BE SUPPORTED AT EACH BRANCH CONNECTION AND AT EVERY 4' VENT PIPING CANNOT BE UNDER STRAIN AND SHALL BE CORRECTLY GRADED. COPPER PIPING INSTALLED HORIZONTALLY AT THE SAME LEVEL CANNOT HAVE BRANCH LINES THAT HIT, PROPER USE OF FITTINGS IS REQUIRED TO OFFSET AROUND OTHER PIPES. |
|
| 04/10/2006 | PLUMBING - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/04/2006 | PLUMBING - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |