Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/08/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/03/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* NO ONE ON SITE -- LOCKED! |
|
| 04/28/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* NOT UNDER TEST. HORIZONTAL TO HORIZONTAL CHANGES OF DIRECTION REQUIRE LONG RADIUS 90 DEGRESS INSTALL SWEEP |
|
| 04/27/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* ABS TO PVC TRANSITION GLUE IS ONLY LISTED TO BE USED OUTDOORS. RANDOM INTERMINGLING OF MATERIALS IS NOT ACCEPTABLE. |
|
| 04/26/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CLOSET FLANGE -- OK 3" VENT CORRECTED MORE HANGERS ON HORIZONTAL PIPING ABOVE CEILING ARE NEEDED. GAS PIPING NOT COMPLETED. |
|
| 04/14/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 04/10/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DWV IN WALLS OK OVERHEAD VENTING REQUIRES SUPPORT. VENT SHALL BE FLAT OR GRADED BACK TOWARDS FIXTURE BACKPITCH IS PRESENT ON 3" VENT DO NOT STRAIN PIPING COPPER IN WALLS OK OVERHEAD COPPER REQUIRES SUPPORT EVERY 6' DO NOT BEND OR STRAIN TUBING. HOT AND COLD LINES SHOULD NOT TOUCH. REMOVE BELL REDUCER IN RUN. REDUCE AT TEES, ACCORDING TO PLAN. WIPE EXCESS FLUX FROM JOINTS ISOLATE COPPER FROM METAL. GAS PIPING INSTALLED TO ANSUL AT CEILING LOCATION, TO DROP IN WALL TO HOT FOOD WELL LOCATION, PIPING NOT COMPLETED IN WALL AT HOT FOOD LOCATION. PIPING OVERHEAD EXCEPT FOR RISERS THRU ROOF. PROVIDE SUPPORT IN ALL SECTIONS. PRESSURE TEST OK. RETEST AFTER COMPLETING GAS PIPING CLOSET FLANGE OK |
|
| 04/04/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/10/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) 1/2 HOT AND COLD WATER TYPE L SOFT W TO 2/P-1 HAND SINK 2) FLOOR SINKS INSTALLED WITH MISSION COUPLINGS |