Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
05/08/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
05/03/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
NO ONE ON SITE -- LOCKED!
04/28/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
NOT UNDER TEST.
HORIZONTAL TO HORIZONTAL CHANGES OF DIRECTION REQUIRE LONG RADIUS 90 DEGRESS
INSTALL SWEEP
04/27/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
ABS TO PVC TRANSITION GLUE IS ONLY LISTED TO BE USED OUTDOORS.
RANDOM INTERMINGLING OF MATERIALS IS NOT ACCEPTABLE.
04/26/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
CLOSET FLANGE -- OK
3" VENT CORRECTED
MORE HANGERS ON HORIZONTAL PIPING ABOVE CEILING ARE NEEDED.
GAS PIPING NOT COMPLETED.
04/14/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/10/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV IN WALLS OK
OVERHEAD VENTING REQUIRES SUPPORT.
VENT SHALL BE FLAT OR GRADED BACK TOWARDS FIXTURE
BACKPITCH IS PRESENT ON 3" VENT
DO NOT STRAIN PIPING
COPPER IN WALLS OK
OVERHEAD COPPER REQUIRES SUPPORT EVERY 6'
DO NOT BEND OR STRAIN TUBING.
HOT AND COLD LINES SHOULD NOT TOUCH.
REMOVE BELL REDUCER IN RUN. REDUCE AT TEES, ACCORDING TO PLAN.
WIPE EXCESS FLUX FROM JOINTS
ISOLATE COPPER FROM METAL.
GAS PIPING INSTALLED TO ANSUL AT CEILING LOCATION, TO DROP IN WALL TO HOT FOOD WELL LOCATION, PIPING NOT COMPLETED IN WALL AT HOT FOOD LOCATION. PIPING OVERHEAD EXCEPT FOR RISERS THRU ROOF.
PROVIDE SUPPORT IN ALL SECTIONS.
PRESSURE TEST OK. RETEST AFTER COMPLETING GAS PIPING
CLOSET FLANGE OK
04/04/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
01/10/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) 1/2 HOT AND COLD WATER TYPE L SOFT W TO 2/P-1 HAND SINK
2) FLOOR SINKS INSTALLED WITH MISSION COUPLINGS