Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/16/2006 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 08/15/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | ||
| 04/14/2006 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* COMPLETE PANEL MAKE UP |
|
| 04/10/2006 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* NOTES 1. EQUIP. GROUND FOR BOND BUSHINGS IN GUTTER TO SMALL SIZE SIZE FOR 350 MCM. 2. INSTALL FUSES & REJECTION PINS IN SERVICE DISCONNECTS. |
|
| 03/31/2006 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* INSTALL MAIN BOND JUMPER FOR NEUTRAL TO GROUND AT SERVICE OK WATER & GAS PIPE BONDING. |