Permit: T05CM05189

Parcel: 13824164B

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/16/2006 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
08/15/2006 ELECTRIC - SERVICE UPGRADE Partial Approval
04/14/2006 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
COMPLETE PANEL MAKE UP
04/10/2006 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
NOTES
1. EQUIP. GROUND FOR BOND BUSHINGS IN GUTTER TO SMALL SIZE SIZE FOR 350 MCM.
2. INSTALL FUSES & REJECTION PINS IN SERVICE DISCONNECTS.
03/31/2006 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
INSTALL MAIN BOND JUMPER FOR NEUTRAL TO GROUND AT SERVICE
OK WATER & GAS PIPE BONDING.