Inspection History Details
Permit: T05CM05186
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/27/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 12/22/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* TRANSFORMER - UFER - COPPER #4 FROM GROUND RODS IS REQUIRED TO TIE INTO NEW NEUTRAL - NOW UFER TIED TO FRAME OF TRANSFORMER AT A DIFFERENT LOCATION CANNOT GO THRU FRAME TO BRING TOGETHER |