Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T05CM05186


Addresses:

1001 W ROGER RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/27/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
12/22/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
TRANSFORMER - UFER - COPPER #4 FROM GROUND RODS IS REQUIRED TO TIE INTO NEW NEUTRAL - NOW UFER TIED TO FRAME OF TRANSFORMER AT A DIFFERENT LOCATION
CANNOT GO THRU FRAME TO BRING TOGETHER