Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T05CM05175
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/13/2006 | MECHANICAL - ABOVE CEILING | Approved | BANDING A FIRE WRAP NOT PER SPECS. INSPECTED FIRE WRAP. OK TO COVER | |
01/10/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) PLANS SHOW NO DETAILS FOR TYPE I AND II HOODS THE WOOD BURNING PIZZA OVEN IS REQUIRED TO HAVE A TYPE I HOOD AND DUCT. SEE SECTION 507.2.1 2003 IMC. PROVIDE COMPLETE INSTALL INSTRUCTIONS 20 OK TO SHEETROCK AREAS EXCEPT KITCHEN |