Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM05175
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/17/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
03/16/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
03/14/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. WATER HEATER DISCONNECT TO HAVE WORKING CLEARANCES. ALSO DOOR NEEDS TO OPEN 90 DEGREES. 2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20 3. DISHWASHER RECEPTACLE TO USE A WET LOCATION COVER 4. CONDUCTORS LARGER THAN #8 NEED PLASTIC BUSHINGS 5. EM LIGHTING TO BE ON CIRCUIT FOR LIGHTING SERVING AREA 700.12 6. SUPPORT M/C CABLE WITHIN 12" OF BOX 7. USE LISTED SPLICE CONNECTOR FOR GROUNDS IN INTER LOCK BOX. OK ROOF |