Permit: T05CM05175

Parcel: 11004345J


Addresses:

3305 N SWAN RD #105

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/11/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
OK WALLS AND HARD CEILINGS
RECEIVED LETTER FOR M/C CABLE AND CONDUIT
01/10/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. JUNCTION BOXES TO BE ACCESSIBLE
2. SUPPORT M/C CABLE WITHIN 12" OF BOXES
3. TIGHTEN LOOSE FITTINGS
4. PLANS CALL FOR 3/4" CONDUIT - NO EXCEPTIONS