Permit: T05CM05168

Parcel: 14117005C


Addresses:

7335 S HOUGHTON RD


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T05CM05168

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/04/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
01/09/2008 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
JUST NEED CORRECT R.V DUMP STATION TERMINATION CAP
12/28/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
SEAL PIPE PENETRATIONS INTO & OUT OF BLD.
COMPLETE ITEMS #4, 5, 6, 8, 9
CORRECTLY OR YOU COULD BE REFEE'D
12/12/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. SHALL LABEL ALL BACKFLOW DEVICES
2. PROVIDE CORRECT BACKFLOW PROTECTION FOR CHEMICAL ADDITION AT MOP SINK OR SEPARATE WATER SUPPLY
3. EXPOSE TRAP PRIMER VALVE FOR REST AREA
4. PROVIDE ACCESS PANEL AT ICE MACHINE
5. PROVIDE PROPERLY VENTED FLOW CONTROL FOR GREASE INTERCEPTOR
6. PROVIDE CORRECT DRAINAGE FOR WASH & RINSE BOWL TO INTERCEPTOR SANITIZE BOWL TO BE INDIRECT DRAIN
7. COMPLETE INSULATION FOR HOT & HOT RETURN PIPING
8. SUPPORT & SECURE EXPANSION TANK AT WATER HEATER
CLEAN BACTERIA REPORT TO GO TO BLD INSPECTOR
9. PROVIDE DETAIL FROM ENGINEER FOR DUMP STATION
12/11/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
COMPLETE ALL PLUMBING INSTALLS INCLUDING APPLIANCES, CERTIFICATIONS FOR ALL DEVICES, CLEAN BACTERIA REPORT ETC.

FAILURE TO COMPLY SHALL RESULT IN REINSPECTION FEES

NOT A COMPLETE LIST
12/10/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
WATER TO BE ON TO ALL FIXTURES, COMPLETE ALL PLUMBING WORK INCLUDING APPLIANCE INSTALLS WITH ALL CORRECT BACKFLOW DEVICES.