Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM05168

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/16/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
RECEIVED LETTER OF TORQUE FOR SWITCH GEAR
01/15/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. HAVE ELECTRICAL CONTRACTOR ON SITE TO OPEN PANELS AND SWITCH GEAR
2. VENDING MACHINE LISTED FOR INDOOR USE ONLY
3. RECALL WHEN READY
01/04/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) PROVIDE LETTER OF TORQUE FOR TERMINATIONS IN SWITCH GEAR
2) BOND GAS AND WATER AFTER SWING OVER COMPLETE
3) RECALL AFTER SWING OVER COMPLETE AND GENERATOR REMOVED
4) HAVE ENGINEER PROVIDE LETTER FOR CHANGE IN SERVICE ENTRANCE CONDUCTOR SIZES
12/19/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. CONNECT GROUNDING CONDUCTORS TO LIGHT POLES
2. CANNOT RUN LOW VOLTAGE WIRING WITH HIGH VOLTAGE
NEED TO BE IN SEPARATE RACEWAY
3. USE PROPER FITTINGS FOR CONNECTION TO PVC
12/12/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. WIRE SLUSHIE MACHINE
2. NEED PANEL DIRECTORIES
3. NEED TO INSTALL POLE LIGHTS
4. INSTALL LUGS FOR GROUNDING ROOFTOP JUNCTION BOXES
5. DISCONNECT FOR HW RECIRC.
6. OK OUTDOOR LIGHTING ON BUILDING & IN CANOPY
7. INSTALL LOCKOUT MEANS FOR INTERIOR SIGNS
12/11/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. OK POLE BASES
2. OK SEAL OFFS. FUEL ELECTRIC OK.
3. RECEIVED LETTER FOR ESTOP SYSTEM
4. EM LIGHTING NOT PER PLAN. EM LIGHTS BACK OF STORE NOT WORKING
5. CANNOT USE SHEETMETAL SCREWS FOR GROUNDING
6. INSTALL BONDING SCREW IN DISCONNECTS
7. GROUND SAT DISHES
8. INSTALL SEALED COVERS AND RECEPT IN FRONT RAISED FLOOR
9. INSTALL ALL SCREWS IN INDUSTRIAL COVERS
10. NEED PANEL SCHEDULES
11. WIRE ROOFTOP UNIT
12. WIRES COMING OUT OF SIDE OF LIGHT BACK OF STORE
13. INSTALL ALL EQUIPMENT
14. SEE LAST PAGE FOR SIGN LIGHTING ISSUES

INTERIOR SIGNS:
1. GTO NOT ALLOWED IN WALL CAVITY
2. TIGHTEN LOOSE FITTINGS
3. BOND FLEX RACEWAYS (600.7)
4. SWITCHES TO BE CAPABLE OF BEING LOCKED OUT (600.6)
5. MARKING LABELS AS PER 600.4
6. GTO & BOOT - VERIFY FROM MANUFACTURE FOR PAINT
12/10/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. OK PACKING IN SEAL OFFS
2. ELECTRICAL CONTRACTOR TO GO THROUGH ENTIRE JOB AND CHECK ALL WORK
3. OK 2 POLE BASES NORTH ENTRY, 1 BASE WEST ENTRY
1 BASE BY TRASH AREA