Permit: T05CM05168

Parcel: 14117005C


Addresses:

7335 S HOUGHTON RD

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
01/16/2008 ELECTRIC - UFER Approved IVRS - Inspection :*
08/17/2007 ELECTRIC - UFER Partial Approval IVRS - Inspection :*
1. OK 3/0 COPPER TO REBAR IN FOOTING
2. OK 2" PVC FOR TEMP SERVICE
08/16/2007 ELECTRIC - UFER Denied IVRS - Inspection :
The grounding electrode conductor is not installed per code.| 220*
1. GROUND CLAMPS TO BE LISTED FOR USE ON #4 REBAR
AND DIRECT BURY. TERMINATE WIRE PROPERLY ON CLAMP NEC 250.70