Permit: T05CM05161

Parcel: 10511040D

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM05161

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/29/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/22/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245
1 REDO PANEL DIRECTORY SO IT IS IDENTIFIED CORRECTLY AND LEGIBLE - NEC 408.4
2. TIGHTEN ALL LOOSE DEVICES IN WALLS AND USE BOX EXTENSION IF REQUIRED -- NEC 406.4
3. EMERGENCY LIGHTING IS NOT WORKING PER PLAN?
4. HAVE OVERFILLED 4SQ ABOVE PANEL IN CEILING INSTALL BOX EXTENSION IN THIS ONE AND OTHERS AS REQUIRED
NEC 314.16
5. PLAN CALLS FOR DEDICATED CKT TO WATER CIRC. PUMP

NOTE: EMERGENCY LIGHTING TO BE ON CKT IN THAT AREA NEC 700.12(E)