Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM05161
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/29/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/22/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245 1 REDO PANEL DIRECTORY SO IT IS IDENTIFIED CORRECTLY AND LEGIBLE - NEC 408.4 2. TIGHTEN ALL LOOSE DEVICES IN WALLS AND USE BOX EXTENSION IF REQUIRED -- NEC 406.4 3. EMERGENCY LIGHTING IS NOT WORKING PER PLAN? 4. HAVE OVERFILLED 4SQ ABOVE PANEL IN CEILING INSTALL BOX EXTENSION IN THIS ONE AND OTHERS AS REQUIRED NEC 314.16 5. PLAN CALLS FOR DEDICATED CKT TO WATER CIRC. PUMP NOTE: EMERGENCY LIGHTING TO BE ON CKT IN THAT AREA NEC 700.12(E) |