Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM05156
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/25/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) NOTE: IDENTIFY SERIES RATED SYSTEM AS PER PLAN-CALL IN WHEN COMPLETE |
|
01/06/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) NEED MINIMUM #4 CU CONDUCTOR FOR GROUNDING ELECTRODE TAP AND CONNECT IT DIRECTLY TO GROUNDING ELECTRODE CONDUCTOR-NOT ENCLOSURE 2) STRAP RACEWAY ABOVE PANEL ON EXTERIOR WALL 3) SEAL ALL UNUSED OPENINGS IN PANEL 4) GROUND PANEL ENCLOSURE-(GROUND BAR IS ISOLATED) 5) INSTALL ADDRESS LABEL FOR SERVICE 6) IDENTIFY SERIES RATED SYSTEM PER NEC 110.22 7) PROVIDE DISCONNECTION MEANS FOR EQUIPMENT (CHT11ER) ETC... AS REQUIRED PER NEC 430 |
|
11/17/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :*ID-DISCONNECT & PANEL OUTSIDE ( ON OUTSIDE COVER) DISCON CONTAINS R FUSES-REJECT PINS REQUIRE INSTALL CORRECT SIZE SCREW FOR PNL-R COVER INSTALL STRAP ON 1 1/4 RISER OUT OF PNL R |