Permit: T05CM05156

Parcel: 11613195E


Addresses:

1735 W SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM05156

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/25/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) NOTE: IDENTIFY SERIES RATED SYSTEM AS PER PLAN-CALL IN WHEN COMPLETE
01/06/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) NEED MINIMUM #4 CU CONDUCTOR FOR GROUNDING ELECTRODE TAP AND CONNECT IT DIRECTLY TO GROUNDING ELECTRODE CONDUCTOR-NOT ENCLOSURE
2) STRAP RACEWAY ABOVE PANEL ON EXTERIOR WALL
3) SEAL ALL UNUSED OPENINGS IN PANEL
4) GROUND PANEL ENCLOSURE-(GROUND BAR IS ISOLATED)
5) INSTALL ADDRESS LABEL FOR SERVICE
6) IDENTIFY SERIES RATED SYSTEM PER NEC 110.22
7) PROVIDE DISCONNECTION MEANS FOR EQUIPMENT (CHT11ER) ETC... AS REQUIRED PER NEC 430
11/17/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*ID-DISCONNECT & PANEL OUTSIDE ( ON OUTSIDE COVER)
DISCON CONTAINS R FUSES-REJECT PINS REQUIRE
INSTALL CORRECT SIZE SCREW FOR PNL-R COVER INSTALL STRAP ON 1 1/4 RISER OUT OF PNL R