Permit: T05CM05135

Parcel: 13409019L

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/29/2005 PLUMBING - FINAL Approved
11/18/2005 PLUMBING - FINAL Partial Approval PARTIAL APPROVAL NO PROBLEM FOR TEMP C/0
11/17/2005 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
11/16/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE CHECK VALVE AT IMMEDIATE DISCHARGE OF PUMP ON FOOT SPA PER PLAN
2) PROVIDE RIDGID PIPING FOR THIS DRAIN TO APPROVED ELEVATED FLOOR SINK AND SECURE PROPERLY
3) TERMINATE BACKFLOW DEVICE DRAINS INTO THIS FLOOR SINK
4) WATER HEATER TEMPERATURE AND PRESSSURE RELIEF DRAIN TO TERMINATE AT 90 DEGREE DOWN 6" TO 24" FROM FINISH ELEVATION
11/15/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*18" MINIMUM REQUIRED FOR STANDPIPE DRAIN ( FROM TRAP SEAL TO TOP OF STANDPIPE)
R.P.G DRAINS MUST DRAIN INTO SAME STANDPIPE NOT INTO SIDE FITTING
BRANCH TAIL PIECE UNDER SINK IS NOT LISTED FOR HORIZONTAL POSITION.
11/14/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*NOT READY
PLEASE CALL IN ALL REQUIRED INSPECTIONS PRIOR TO CALLING FINAL