Permit: T05CM05124

Parcel: 140420150


Addresses:

2660 E MEDINA RD

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
10/29/2007 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
10/17/2007 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
ALL PVC PIPING TO BE PRIMED & GLUED WITH APPROVED PVC PRIMER & GLUE
10/09/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
WELDING AND WRAPPING OF STOVE HOOD OK
08/10/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) GATE HOUSE OK TO SHEETROCK ALL HARD LIDS
2) MAINTAIN MIN 24" CLEARANCE TO SERVICE FAN COILS (GREASE DUCT OK TO FIRE WRAP)
07/19/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
SEAL ALL JOINTS
CONDENSATE DRAINS OK
SUSPENDED ROUGH DUCT OK TO PROCEED
PROVIDE MIN. 20 X 30 ACCESS OPENING TO FAN COILS
PROVIDE BACKING
07/12/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO SHEETROCK 1ST & 2ND FLOOR STUDIOS
STILL NEED TO SEE FIRE DAMPERS & DUCTING FOR ALL COMMON AREAS.
06/08/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
POOL HOUSE OK FOR SHEETROCK
06/07/2007 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
INCOMPLETE WORK
06/01/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
3RD FLOOR STUDIOS OK TO SHEETROCK