Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/27/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 10/25/2007 | PLUMBING - INTERMEDIATE | Cancelled | IVRS - RI canceled | |
| 10/18/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* GATE HOUSE OK |
|
| 10/17/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* REPAIR LEAK ON SHOWER DRAIN IN ROOM #330, 333 |
|
| 10/15/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. ROOM #328 SHOWER OK ONLY 2. FIRST FLOOR OVERHEAD IN HALLWAY OK |
|
| 10/11/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. LOBBY RESTROOM CLOSET FLANGE OK 2. POOL HOUSE CLOSET FLANGE OK 3. ADD SUPPORT FOR WATER HEATER PIPING DOWN HALLWAY ON FIRST FLOOR PIPING INTO ROOMS |
|
| 10/09/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
| 10/08/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* PROVIDE WATER TEST SHOWERS |
|
| 10/05/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 10/02/2007 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SHALL PROVIDE CORRECT DRAINAGE FOR SHOWER & FLOOR DRAIN 2. SHALL PROVIDE CORRECT TRANSITION CONNECTION OR PVC DRAINS FOR PVC PIPING 3. FLOOR PANS SHALL HOLD WATER TEST |
|
| 09/26/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 2ND LEVEL CLOSET FLANGES OK |
|
| 09/25/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* DISCUSSED SHOWER PAN LINER INSTALL WITH SCOTT (TILE SETTER), DOMINIC (PLUMBER) AND GAVE HANDOUT FOR CORRECT INSTALL |
|
| 09/24/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* SCOTT GREEN TEXAS CUSTOM DRAIN WATER PROOFING HANDOUT GIVEN - SHALL INSTALL CORRECTLY WITH TEST PER HANDOUT |
|
| 09/21/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CONTINUED NOT READY WILL RESULT IN REINSPECTION FEE |
|
| 09/20/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 09/18/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* PROVIDE TEST ON SHOWERS |
|
| 09/10/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1ST FLOOR CLOSET FLANGES INSPECTION OTHER THAN SHOWER ROOM OK |
|
| 09/04/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
| 08/31/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CLOSET FLANGES ON 3RD FLOOR OK OTHER THAN #329 & #330 |
|
| 08/27/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* NORTH SOUTH WIND FROM NORTH SIDE TO #329 CLOSET FLANGES OTHER THAN #330 OK 3RD FLOOR ONLY |
|
| 07/24/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* STORAGE ROOM #152 AND WATER SOFTENER ROOM #155 OVERHEAD PIPING TO ROOM #155 OK |
|
| 07/18/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. GAS PSI TEST OK 2. GATE HOUSE IN WALL TEST ON WATER WASTE & VENT OK |
|
| 07/16/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. GATE HOUSE WASTE AND VENT TEST OK 2. EAST/WEST WING WATER PIPING OK |
|
| 07/13/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* REPAIR LEAK FOR TEST FROM TOOM #209 AND #21 |
|
| 07/12/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. FIRST FLOOR TUB OK 2. LAUNDRY FIRST FLOOR OK WATER PIPING 3. EMPLOYEE LOUNGE FIRST FLOOR WATER PIPING OK |
|
| 07/05/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. UNCOVER 3RD FLOOR PLUMBING WALL ON EAST/WEST WING 2. 2ND FLOOR PLUMBING IN WALL OK |
|
| 07/02/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. 3RD FLOOR 2ND FLOOR NORTH SOUTH WIND OK WASTE VENT & WATER 2. 1ST FLOOR OK WASTE VENT & WATER TO ELEVATOR NORTH SOUTH WING. |
|
| 06/29/2007 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* WORK COVERED WITHOUT INSPECTION |
|
| 06/21/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
| 06/19/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* PROVIDE TEST ON WATER PIPING PROVIDE APPROVED PLANS |
|
| 06/11/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* SHALL PROVIDE WATER TEST ON CPVC WATER PIPING (NO AIR TESTING OF PLASTIC PIPING) SHALL SECURE ALL PIPING CORRECTLY |
|
| 06/06/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 2ND FLOOR TUB WASTE TRAPS OK |
|
| 06/05/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* FILL PIPING AND TUBS FOR TEST |
|
| 06/04/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
| 05/29/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* TUBS WASTE TRAPS 3RD FLOOR EAST WEST WING OK |
|
| 05/25/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. 324 REPAIR LEAK ON TUB TRAP 2. NORTH-SOUTH WINK TUB TRAPS OK 3RD FLOOR REPAIR #324 |
|
| 05/14/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PARTIAL PER REDLINES TO BE APPROVED AT LATER DATE DO NOT COVER WALLS OK TO SET TUBS ON THIRD FLOOR WASTE & VENT TEST OK |
|
| 05/11/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* PROVIDE TEST ON PIPING FOR INSPECTION |
|
| 05/10/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* PARTIAL APPROVAL FOR UNDERGROUND GAS PIPING P.E PER RUSSELL WING FROM HALFF ASSOCIATES |
|
| 05/09/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* TUBS ON 2ND FLOOR FROM NORTHSIDE TO ROOM #331 TEST OK |
|
| 05/08/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. PSI TEST ON UNDERGROUND P.E GAS PIPING WITH TRACER WIRE OK 2. PARTIAL APPROVAL FOR REDLINE DRAWING EAST SIDE FRIG FLOOR NORTHSIDE TO 134 |
|
| 05/04/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* FILL TUBS FULL FOR TEST ON TUB WASTE AND OVERFLOW |
|
| 05/02/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. TUBS PIPING TO BE FOR DRAIN 2. PROVIDE APPROVAL PLANS FOR WASTE & VENT PIPING |
|
| 04/30/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. ROOMS 133, 134, 135, 136, 137, 138 TEST OK ON WASTE & VENT PER REDLINES PROVIDE APPROVED DRAWING FROM CITY OF TUCSON. |
|
| 04/27/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* NOT INSTALLED PER APPROVED PLAN WATER TEST IN PLACE ON WASTE & VENT SYSTEM THRU ROOF UNITS 139 THRU 144 1ST LEVEL & ABOVE 1. SHALL PROVIDE CITY APPROVED REVISED ISOMETRIC PLAN OF ACTUAL INSTALLATION FOR WASTE & VENT SYSTEM BEFORE COVERING ANY WORK. FOR SIZING, CLEANOUTS, POSSIBLE WET VENTING OF FIXTURES. |
|
| 04/05/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* WALK THRU WITH PLUMBER |