Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/07/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/27/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK DIST. PANELS & SUB-PANEL MAKE-UP 3RD FL. |
|
| 09/11/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) ONLY AUTHORIZED PERSONAL TO HAVE ACCESS TO ELECTRICAL EQUIPMENT. DO NOT ENERGIZE BEYOND SERVICE PRIOR TO INSPECTOR APPROVAL 2) PLEASE CHECK NOTES ON PREVIOUS INSPECTION. NOTE #2 FROM 8/30/07 |
|
| 08/30/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - OK TO CLOSE UP ELEC. EQUIP. IN 1ST FLOOR ELEC. ROOM POST BOND FOR TEMP POWER FOR TEST - ENTRANCE TO WORK SPACE TO MEET REQUIREMENTS OF 110.33 NEC |
|
| 08/29/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* LABEL BREAKERS CALL FOR INSP. |
|
| 07/20/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - OK ELECTRICAL ROUGH IN WALLS FOR GATE HOUSE AREA - FIRE ALARM/SIGNAL CIRCUITS & LOW VOLTAGE CABLING TO COMPLY WITH ART. 760, 725, 800 NEC EMT CONNECTOR NOT APPROVED AS SLEEVE FOR CABLING. |
|
| 07/13/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - RECEIVED LETTER FOR FEEDINGS - OK 1ST FLOOR ROOMS EXCEPT CORRIDORS, ELECTRIC ROOM |
|
| 06/18/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROUGH PARTIAL 2ND FLOOR, CALL FOR INSP. AFTER FEEDER FOR PANELS ARE INSTALLED |
|
| 06/04/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PARTIAL OK WALLS EXCEPT AT PANEL LOCATION, EQUIP. ROOM WILL BE SURFACE RACEWAYS. |
|
| 05/25/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROUGH WIRING -- SUBJECT TO REVISION AND C.O.T APPROVAL FOR PANEL FEEDER CHANGES, SIZE & CONDUCTOR MATERIAL, PANELS HAVE ALUM. BUSSING INSTEAD OF COPPER MAIN LUGS. |
|
| 05/23/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - 3RD FLOOR ROUGH PARTIAL - COMPLETE INSTALL OF NAIL PLATE PROTECTION OVER SUB-PANELS. - WILL DISCUSS AS BUILDING FOR PANEL FEEDERS, SPEC'S FOR COPPER/ALUM INSTALL WITH SENIOR INSPECTOR. - RECEIVED LETTER FOR ROMEX USAGE. |
|
| 05/10/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROUGH FOR OUTSIDE STOREROOM, 2 - 2" U.G FEEDERS TO STOREROOM FROM SES, U.G CONDUITS FOR LIGHT POLES AT ENTRY AREA & SIGN SUPERINTENDENT WILL PROVIDE LETTER FROM ARCH. FOR USE OF ROMEX |
|
| 04/16/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1ST FLOOR 1. PLEASE VERIFY WITH ENGINEER OF RECORD FOR APPROVAL OF PANEL FEEDER SIZES & MATERIAL CU. AL? PLANS CALL FOR #1 CONTR. INSTALLED #2 AL, FOR PANEL FEEDERS. 2. ROUGH WIRING APPROVAL SUBJECT TO ABOVE NOTE COMPLETE FOR CABLING. |
|
| 04/06/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK REMAINDER OF PARKING LOT LTG |
|
| 04/05/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WIRING METHOD FOR AIR HANDLERS IN UNITS (HVAC CLOSET) |
|
| 03/16/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE INSTALL PANEL & FEEDER 2. INSTALL FLEX OVER AC FEEDER & NAIL TO STUD & PROTECT ROMEX ENTRY AT FLEX 3. BOX FOR FAN EXHAUST & LIGHT TO BE INSTALLED 4. FIRESTOP UL LISTED & APPROVED. |