Permit: T05CM05124

Parcel: 140420150


Addresses:

2660 E MEDINA RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
12/07/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/27/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK DIST. PANELS & SUB-PANEL MAKE-UP 3RD FL.
09/11/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) ONLY AUTHORIZED PERSONAL TO HAVE ACCESS TO ELECTRICAL EQUIPMENT. DO NOT ENERGIZE BEYOND SERVICE PRIOR TO INSPECTOR APPROVAL
2) PLEASE CHECK NOTES ON PREVIOUS INSPECTION. NOTE #2 FROM 8/30/07
08/30/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- OK TO CLOSE UP ELEC. EQUIP. IN 1ST FLOOR ELEC. ROOM
POST BOND FOR TEMP POWER FOR TEST
- ENTRANCE TO WORK SPACE TO MEET REQUIREMENTS OF 110.33 NEC
08/29/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
LABEL BREAKERS CALL FOR INSP.
07/20/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- OK ELECTRICAL ROUGH IN WALLS FOR GATE HOUSE AREA
- FIRE ALARM/SIGNAL CIRCUITS & LOW VOLTAGE CABLING TO COMPLY WITH ART. 760, 725, 800 NEC EMT CONNECTOR NOT APPROVED AS SLEEVE FOR CABLING.
07/13/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- RECEIVED LETTER FOR FEEDINGS
- OK 1ST FLOOR ROOMS EXCEPT CORRIDORS, ELECTRIC ROOM
06/18/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROUGH PARTIAL 2ND FLOOR, CALL FOR INSP. AFTER FEEDER FOR PANELS ARE INSTALLED
06/04/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
PARTIAL OK WALLS EXCEPT AT PANEL LOCATION,
EQUIP. ROOM WILL BE SURFACE RACEWAYS.
05/25/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROUGH WIRING -- SUBJECT TO REVISION AND C.O.T APPROVAL FOR PANEL FEEDER CHANGES, SIZE & CONDUCTOR MATERIAL, PANELS HAVE ALUM. BUSSING INSTEAD OF COPPER
MAIN LUGS.
05/23/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
- 3RD FLOOR ROUGH PARTIAL - COMPLETE INSTALL OF NAIL PLATE PROTECTION OVER SUB-PANELS.
- WILL DISCUSS AS BUILDING FOR PANEL FEEDERS, SPEC'S FOR COPPER/ALUM INSTALL WITH SENIOR INSPECTOR.
- RECEIVED LETTER FOR ROMEX USAGE.
05/10/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROUGH FOR OUTSIDE STOREROOM, 2 - 2" U.G
FEEDERS TO STOREROOM FROM SES, U.G CONDUITS FOR LIGHT POLES AT ENTRY AREA & SIGN
SUPERINTENDENT WILL PROVIDE LETTER FROM ARCH. FOR USE OF ROMEX
04/16/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1ST FLOOR
1. PLEASE VERIFY WITH ENGINEER OF RECORD FOR APPROVAL OF PANEL FEEDER SIZES & MATERIAL CU. AL?
PLANS CALL FOR #1 CONTR. INSTALLED #2 AL, FOR PANEL FEEDERS.
2. ROUGH WIRING APPROVAL SUBJECT TO ABOVE NOTE COMPLETE FOR CABLING.
04/06/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK REMAINDER OF PARKING LOT LTG
04/05/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WIRING METHOD FOR AIR HANDLERS IN UNITS (HVAC CLOSET)
03/16/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. PLEASE INSTALL PANEL & FEEDER
2. INSTALL FLEX OVER AC FEEDER & NAIL TO STUD & PROTECT ROMEX ENTRY AT FLEX
3. BOX FOR FAN EXHAUST & LIGHT TO BE INSTALLED
4. FIRESTOP UL LISTED & APPROVED.