Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/07/2007 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 02/15/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK REMAINDER OF 4" SECONDARY'S FROM NORTH BLD. WALL TO TEP X-FORMER |
|
| 02/05/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK LOW VOLTAGE, DATA, COMM, 2" PVC TO FRONT DESK |
|
| 01/16/2007 | ELECTRIC - UNDERGROUND | Partial Approval | 1. PER 300.12 NEC REQUIRES RACEWAYS TO BE CONTINUOUS ALSO, SEE ART. 314.15 PROVIDE APPROVED & STAMPED BY ENGINEER CUT SHEET OR PLAN FOR METHOD USED TO ENTER SES. 2. OK PVC CONDUITS & STUB UPS INTO PHONE CLOSET & STUB OUT TO OFFICE/FRONT DESK JOE NATIONAL ELECTRICAL CONTRACTORS 574-532-5019 |
|
| 01/09/2007 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
| 01/05/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1. PARTIAL U.G PANEL FEEDERS & DATA, FA TO POOL BLD. FROM ELEVATOR AREA. ' ALSO, 4" & 2" TO NORTH BLD. EXTERIOR WALL |
|
| 01/04/2007 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* |