Permit: T05CM05124

Parcel: 140420150


Addresses:

2660 E MEDINA RD

Inspection Status: Approved

Inspection History: BUILDING ABOVE CEILING

Date Description Inspector Results Comments
10/16/2007 BUILDING ABOVE CEILING Approved IVRS - Inspection :*
10/11/2007 BUILDING ABOVE CEILING Partial Approval IVRS - Inspection :*
10/11/2007 BUILDING ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
FIX FIRESTOP
07/11/2007 BUILDING ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
06/05/2007 BUILDING ABOVE CEILING Partial Approval IVRS - Inspection :*
IN ACCORDANCE WITH 717.2

NOTE: PROVIDE FIRE BLOCKING ON ENCLOSED SPACED IN CONNECTION WITH ATTIC IN ACCORDANCE WITH SECTION 717.2.1 FIRE BLOCKING MATERIALS CONSIST OF 2" NOMINAL LUMBER OR TWO THICKNESSES OF 1" NOMINAL LUMBER WITH BROKEN LAP JOINTS OR ONE THICKNESS OF 3/4" WOOD STRUCTURAL PANEL WITH JOINTS BACKED OR 5/8 GYPSUM BOARD TYPE X OR OTHER.
05/11/2007 BUILDING ABOVE CEILING Not ready for Inspection IVRS - Inspection :*