Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/15/2007 | FRAMING | Approved | IVRS - Inspection :* | |
| 07/31/2007 | FRAMING | Partial Approval | IVRS - Inspection :* OK TO COVER GATE HOUSE AFTER INTERMEDIATE APPROVAL 1. ALL FRAMING INSPECTION EXCEPT FOR PATIOS |
|
| 07/24/2007 | FRAMING | Partial Approval | IVRS - Inspection :* FRAMING OK FIRE SEALANT OK OK TO DRYWALL INSTALLATION AFTER INTERMEDIATE APPROVALS ON 2ND FLOOR LEVEL |
|
| 07/19/2007 | FRAMING | Partial Approval | IVRS - Inspection :* OK TO INSULATE WALL ON 2ND FLOOR LEVEL |
|
| 07/17/2007 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
| 07/13/2007 | FRAMING | Partial Approval | IVRS - Inspection :* THIS INSPECTION COVERS FIRST FLOOR LEVEL OK TO COVER -- ELECTRICAL, PLUMBING, MECH. INTERMEDIATES APPROVALS |
|
| 07/12/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* VERIFY AND PROVIDE FIRE SEALANT AROUND PENETRATIONS ON FIRE PARTITION AND CORRIDOR (SPRINKLER SYSTEM LINE) |
|
| 07/06/2007 | FRAMING | Partial Approval | IVRS - Inspection :* THIS INSPECTION COVERS POOLHOUSE |
|
| 07/03/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE SPECIAL INSPECTION REPORT OR A.B INSTALLED AND PROPER SEPARATION -- UNCOVER SECTIONS ON BOTTOM PART OF WALL ON EACH SEPARATE SPACE |
|
| 06/26/2007 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
| 06/22/2007 | FRAMING | Not ready for Inspection | INCOMPLETE | |
| 06/08/2007 | FRAMING | Partial Approval | IVRS - Inspection :* THIS INSPECTION COVERS 3RD LEVEL FLOOR IN ACCORDANCE WITH APPROVED PLANS AND SPEC. OK TO DRYWALL INSTALLATION. |
|
| 06/07/2007 | FRAMING | Partial Approval | IVRS - Inspection :* THIS INSPECTION COVERS STRUCTURAL FRAMING ON THIRD LEVEL FLOOR MUST PROVIDE INSTALLATION OF PUTTY PADS ON ELECTRICAL BOXES, PRIOR TO COVERING OR CONCEALING WALL (FIRE RATED WALL PARTITIONS) |
|
| 06/06/2007 | FRAMING | Partial Approval | IVRS - Inspection :* NOTE: 1. FRAMING/STUCCO COLUMNS FOR POOL IN COMPLIANCE WITH DETAILS ON SHEET A0.3 2. FRAMING FOR ENCLOSURE ELEVATOR APPROVED |
|
| 06/01/2007 | FRAMING | Partial Approval | IVRS - Inspection :* THIS INSPECTION COVERS THIRD LEVEL FLOOR ABOVE CEILING REGARDING 1/2" RC CHANNEL @ 16" O.C PERPENDICULAR TO TRUSSES. |
|
| 05/24/2007 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
| 05/22/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* VERIFY CORRECT BRACING FOR TRUSSES IN ACCORDANCE WITH TRUSSES CALC. SPECIFICATIONS. |
|
| 05/14/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* FRAMING INSPECTION SHALL BE MADE AFTER, ALL FRAMING, FIREBLOCKING AND BRACING ARE IN PLACE AND PIPES, VENTS TO BE CONCEALED ARE COMPLETE AND THE INTERMEDIATE ROUGH ELECTRICAL, MECHANICAL AND PLUMBING ARE APPROVED. |
|
| 05/11/2007 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
| 05/08/2007 | FRAMING | Partial Approval | IVRS - Inspection :* THIS INSPECTION COVERS THE FOLLOWING AREAS 1ST AND SECOND (2ND) FLOOR FOR EXTERIOR METAL CLIPS AND EXTERIOR SHEATHING |
|
| 04/30/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* SHEAR WALLS ON SECTIONS WITH HOLES NEED TO BE REPLACED OR FIXED WITH BLOCKS AROUND EDGES OF BLOCK AND NAILED WITH 4" O.C, SHEAR NEED TO BE AT LEAST 24" WIDTH AND FINISHED ON EDGES WITH BLOCK/NAILING COMPLETE STRAPS ON SHEAR WALL, THIS INSPECTION COVER 1ST AND 2ND FLOORS FOR EXTERIOR SHEAR WALL DESIGN ON SHEET S2.1 |
|
| 04/26/2007 | FRAMING | Partial Approval | IVRS - Inspection :* THIS INSPECTION COVER 3RD FLOOR FOR ALL MECHANICAL ROOMS ON EACH SLEEPING UNIT |
|
| 04/17/2007 | FRAMING | Partial Approval | IVRS - Inspection :* OK TO FILL INS. ON HALLWAY 1ST FLOOR (ENCLOSED SPACE) STORAGE OK TO COVER EXTERIOR POOLHOUSE OK TO COVER EXTERIOR SHEARWALL INSPECTION IN COMPLIANCE WITH DETAILS AND SPEC. ON SHEET S2.1 15/32" RS, NAILING 10d @ 4" O.C |
|
| 04/11/2007 | FRAMING | Partial Approval | IVRS - Inspection :* FIRST FLOOR OK TO DRYWALL INSTALLATION ON MECH. ROOMS PROVIDED HOLDDOWNS HD2A OK SECOND FLOOR -- OK TO DRYWALL INSTALLATION ON MECH ROOMS. |
|
| 04/06/2007 | FRAMING | Partial Approval | IVRS - Inspection :* 1) NOTE: 1ST FLOOR APPROVED MECHANICAL ROOMS-MUST PROVIDE HOLDOWNS BOLTING ? (HD2A) ON EXTERIOR WALL 1ST FLOOR |
|
| 04/05/2007 | FRAMING | Partial Approval | IVRS - Inspection :* FRAMING OK ON MECHANICAL UNITS ON ROOMS 144, 143, 142, 141, 140, 139 , 138, 137, 136, 135, 134, 133, 132, 131, 130, 129 OK TO DRYWALL INSTALLATION PRIOR TO MECHANICAL, ELECTRICAL APPROVALS. DO NOT APPROVE TO TAPE FIRE-RATED ABOVE CEILING AREAS OR OTHERS |
|
| 04/04/2007 | FRAMING | Not ready for Inspection | IVRS - Inspection :* PROVIDE ELECTRICAL, MECHANICAL INTERMEDIATE INSP. APPROVALS |
|
| 02/28/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE TRUSS CALCS IN ACCORDANCE WITH THE NOTE I ON SHEET S4.0 |
|
| 02/22/2007 | FRAMING | Cancelled |