Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T05CM05123
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/01/2006 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* 1) WEST SIDE FURNACE ROOM DUCT UPPER COMB. AIR GRILL TO UPPER 12" OF ROOM 2) FOR FINAL: FURNACE PLENIUM (NEW) NEEDS TO BE SHEETROCKED AS METAL LINED MATERIAL OF NON COMBUSTIBLE MATERIAL |
|
02/03/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. INSULATE SPIRAL SUPPLY AIR DUCTS ABOVE 2ND REST RM CEILING 2. REFRIG LINES DOWN THRU 2ND FLR PLATES/PERTIONS TO 1ST FLR - CHECK ALL COPPER, ISOLATE FROM ANY STEEL FRAMING |