Permit: T05CM05123

Parcel: 11706197A


Addresses:

131 E BROADWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/19/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/17/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK PARTIAL ELECTRICAL FINAL -- OK TO OCCUPY
1. NEED TO SEE SERVICE COMPLETE AND ALL EMERGENCY LIGHTING WORKING FOR COMPLETE FINAL.
03/16/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. IDENTIFY SERVICE DISCONNECTS NEC 230.66 (B)
2. CHECK EMERGENCY AND EXTERIOR LIGHTING TO MAKE SURE PER PLAN
3. PROTECT GROUNDING ELECTRODE CONDUCTOR FROM DAMAGE NEC 250.64 (B)
4. NEED BUSHING 4 AND LARGER WIRE NEC 304.4 (F)
5. IDENTIFY WHITES USED AS HOT NEC 310.12 (C)
03/15/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. HAVE ALL PANELS OPEN FOR INSPECTION
2. SAFE-OFF ALL OPEN WIRING
3. INSTALL ALL COVER PLATES
4. IDENTIFY ALL SERVICE DISCONNECTS & PANEL DIRECTORY'S
CALL WHEN READY
03/06/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK TCO FOR FURNITURE MOVE IN ONLY