Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/19/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/17/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK PARTIAL ELECTRICAL FINAL -- OK TO OCCUPY 1. NEED TO SEE SERVICE COMPLETE AND ALL EMERGENCY LIGHTING WORKING FOR COMPLETE FINAL. |
|
| 03/16/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. IDENTIFY SERVICE DISCONNECTS NEC 230.66 (B) 2. CHECK EMERGENCY AND EXTERIOR LIGHTING TO MAKE SURE PER PLAN 3. PROTECT GROUNDING ELECTRODE CONDUCTOR FROM DAMAGE NEC 250.64 (B) 4. NEED BUSHING 4 AND LARGER WIRE NEC 304.4 (F) 5. IDENTIFY WHITES USED AS HOT NEC 310.12 (C) |
|
| 03/15/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. HAVE ALL PANELS OPEN FOR INSPECTION 2. SAFE-OFF ALL OPEN WIRING 3. INSTALL ALL COVER PLATES 4. IDENTIFY ALL SERVICE DISCONNECTS & PANEL DIRECTORY'S CALL WHEN READY |
|
| 03/06/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK TCO FOR FURNITURE MOVE IN ONLY |