Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/14/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/12/2006 | PLUMBING - INTERMEDIATE | Denied | SAFETY PLATES MISSING AT P3, P1H, P2H AND 4" CLEAN OUT. RECALL WHEN READY FOR INSPECTION. OVERHEAD COPPER NOT PROPERLY SUPPORTED AT EVER 6' AND AT EACH BRANCH CONNECTION AND EVERY ELEVATION CHANGE. ALSO ISOLATE FROM METAL. |
|
| 09/12/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - K TO COVER WALLS - CLOSET FLANGES AND OVERHEAD SUPPORTS LEFT TO COMPLETE. |
|
| 09/08/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ABS UNDER SLAB OK PER CLAYTON ENGINEERING OK TO INSULATE HW PIPING PER SPEC AFTER REMOVING EXCESS FLUX W/A DAMP RAG. INSTALL MISSING SAFETY PLATES RECALL FOR 3035 INSPECTION AFTER COMPLETING. |
|
| 09/07/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* - ROUGH SOIL NOT YET APPROVED - PROVIDE DOCUMENTATION REQUESTED ON 6/29 - CLEANOUTS REQUIRING EXTENSIONS SHALL BE MADE W/WYE PATTERN FITTINGS. - CHANGES OF DIRECTION TO BE SWEEPS - COPPER NOT INSTALLED PER PLAN AT WC AND WH - SAFETY PLATES NEEDED |