Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/08/2006 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* 2 - 4" PAR (FUTURE) TRANSF. TO N. WEST CORNER OF "BEST MAILING" 2 - 4" PAR FEEDS TO BUILDING SERVICE |
|