Permit: T05CM05115

Parcel: 133170630


Addresses:

350 N WILMOT RD


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T05CM05115

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
04/02/2008 ELECTRIC - UNDERGROUND Approved REFERENCE T06CM01872 FOR BULK OF INSPECTIONS ON THIS HOSPITAL ADDITION.
10/26/2007 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
WILL CLOSE AT BUILDING FINAL
12/11/2006 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
- OK 11 SETS OF 4" PVC BEHIND PHYSICAL
- OK 4/0 TO 2 - GROUND RODS.
11/28/2006 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK CONDUITS FOR NURSES STATION 1-L74
10/26/2006 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK CONDUITS UNDER SLAB ROOM 1-L16
OK CADWELD TO GROUND ROD
OK 23 4" PVC TO END OF BUILDING
10/17/2006 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :$
NOT READY 9:15
10/13/2006 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 2 3-4" PVC CONDUITS WITH RIGID 90 DEGREES EAST
20' OK 2 1 1/2" PVC CONDUIT WITH RIGID 90 DEGREES IS 20' EAST ALL OUT OF MAIN ELECTRIC ROOM.
10/12/2006 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
10/11/2006 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK 5 - 4" PVC FROM MAIN ELECT. ROOM TO ELECTRIC 1-24