Permit: T05CM05115

Parcel: 133170630


Addresses:

350 N WILMOT RD


Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Permit Number - T05CM05115

Inspection Description - EXCAVATION/LAYOUT REBAR & ZON

Inspection Status - Approved

Date Description Inspector Results Comments
10/26/2007 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
04/17/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
REINFORCING FOR CURB ON LEVEL 1 PART B-2
GRIDLINE 15.0/R.0-X/14.0-15
03/29/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
FOURTH FLOOR AREA GRIDLINE P-X/1-15 SQ.
HIGH STR. BOLT REPORT PROVIDED
WELDING REPORT PROVIDED
PRE-POUR OBSERVATION REINFORCING FOR FOURTH FLOOR AREA
GRID LINE P-X/1-15 SQ
03/14/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
02/20/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
NOTE: EQUIPMENT PAD ON SECOND FLOOR OK TO POUR
1. GRIDLINE FOR THIRD FLOOR K-P/1.2-15 SHEET S2.EP
2. SUPER STRUCTURE OK AREA B.1 REGARDING TO AREA K-P/1.2-15 WELD, HIGH 5-BOLTS REPORTS PROVIDED.
02/09/2007 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*
01/24/2007 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE ACCESS TO APPROVED PLAN AND IRC IN ACCORDANCE WITH THE SECTION 106.3.1
NO SUPERINTENDENT ON JOB SITE TO PROVIDE INFORMATION ABOUT INSPECTION REQUESTED.
11/29/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
SOUTH, EAST, WEST PERIMETER FOOTINGS OF FOUNDATION
PLAN "B" -- OK TO POUR

ENSURE THAT EXCESS DIRT AND DEBRIS IS REMOVED FROM FOOTINGS.
11/27/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
PEDESTAL #W-15 -- OK TO POUR
11/22/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
FOOTING #W-15
OK TO POUR
11/08/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
1) PEDESTAL W-15, X-15, FOOTING P.8-1 OK TO POUR
11/07/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
FOOTINGS W-15, X-15
PEDESTAL S-15 OK TO POUR
11/06/2006 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*
10:52 AM EXCAVATION AREN'T READY
NO STEEL IN PLACE
NOTHING TO INDICATE YOU WILL BE READY WITHIN 2 HOURS.
11/03/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
1) PIERS X-14, X-13, FOOTINGS V-10, V8, (U-15 ?) OK TO POUR
11/01/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
FOOTINGS @ X-13, X,14
PIERS @ V-2, V-4, V-10, X-9 OK TO POUR
10/31/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
PIER FOOTINGS V-2, V-4
COLUMN FOOTINGS X-9, X-12 OK TO POUR
10/30/2006 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELLED
10/26/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
COLUMN X-1, PIERS X-2, X-5
OK TO POUR
10/25/2006 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE INF. FOR INSP. REQUESTED.
10/23/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
PIERS -- FOOTINGS U-1, W-1 (POURED)
10/20/2006 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*
CANCELLED BY CONTRACTOR
10/19/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
1.7/E.9, D.8, C & 1.5/K WHEN SP. INSP. CONFIRMS
10/18/2006 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*
10/16/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
COLUMN FOOTING U-14 OK TO POUR
10/13/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
COLUMN #V-13 (U-14 NOT READY)
10/12/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
FOOTINGS V-13, T-7; COLUMNS T-3, N-14, N-15
10/11/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
COLUMNS T-10, T-13, M-13; FOOTINGS N-14, N-15, T-3
10/10/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
LINE T/13, 10; LINE U/13
10/09/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
1. PIER CAPS LINE A/5.8, 9.5, 12.5 OK
2. COL. FOOTINGS AT K-11 AND M-11 OK
10/06/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
1. CAISSONS LINE A OK
2. LINE B, C, D, E, F COL FOOTINGS COMPLETE
10/05/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
PIERS #P2, P14, COLUMNS D9.5, B19.5, E9.5
F7.8, F5.8 -- OK TO POUR
10/03/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
LINE B @ 13.8; LINE K @ 7, 14, 15; L @ 15; P @ 7, 13, 15;
Q @ 13, 14; R @ 7, 10, 15; SC1
10/02/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
PIERS: 12.8, F13.8, K13, D5.8
FOOTINGS: B 13.8, D 5.8, K14, K8, J 9.7, P7, R7, R10
09/29/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
LINE F @ 12.8, 13.8; LINE K @ 13, 8
09/28/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
LINE 3 @ 12.5; LINE D @ 5.8, 12.5, 13.8; LINE C 14.3
OK TO PLACE
09/27/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
LINE B - F7 @ 9.5 - F7 @ 12.8; F6.5 @ 14.3
LINE E - F7 @ 13.8
OK TO PLACE FOOTING
09/26/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
F6.5 @ 5.8/B OK TO PLACE
09/12/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval
08/30/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
SOUTH ELEVATOR
PIT NAILS OK TO FINISHED GRADE
08/29/2006 EXCAVATION/LAYOUT REBAR & ZON Cancelled IVRS - RI canceled
08/25/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
SUMP PIT FLOOR OK
08/22/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
SOUTH TUNNEL WALL, LINES R.4/.5 TO R.4/3.8
08/18/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
08/16/2006 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*
FLOODED SITE
08/14/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
08/10/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
N.3 THROUGH G9 -- FORM SAVERS ADDED
08/07/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
4 COLUMN FOOTINGS AT COOLING PLANT OK PER RFI #93
07/28/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
ALL TUNNEL FOOTING OK
OK TO PLACE WHEN SP. INSP. CONFIRMS REMAINING VERTICALS @ SOUTH END.
07/27/2006 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELLED
07/25/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
STEM WALLS TO 0' AFF TUNNEL LINES 2/A-D
07/21/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
SOUTH PORTION OF TUNNEL, LINES B.6/F SOUTH
07/14/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
COLUMNS TO GRADE @ B/1.7 AND N 1.5 OK TO CLOSE & POUR
07/12/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
F4 @ 1.7/B AND F14 @ 1.5/N
07/11/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
07/07/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
06/27/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
EAST WALL OF ELEV. SHAFT @ P/1.8 TO 12' OK
06/22/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
BASEMENT WALL FOOTING C-F/LINE 3
06/16/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
BASEMENT @ ELEVATION 17'0" LINES 1.5-3.9/A.9
CORRIDOR STEP DOWN A.9-C.0
WEST FOOTING INCREASED FROM 18"-24"
06/15/2006 EXCAVATION/LAYOUT REBAR & ZON Cancelled IVRS - RI canceled
06/09/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
BOTTOM OF ELEVATOR @ P/1.7
EAST WALL REQUIRES #6 VERTICALS
NOT #5 REFERENCE DETAIL 13/S3.1
OK TO PLACE WHEN SPECIAL INSP. CONFIRMS REPLACEMENT
PLEASE HAVE SPEC. BOOK SUBMITTAL FOR WATER STOP @ NEXT INSPECTION.
06/08/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
BASEMENT PAD ELEV. 19.6 @ A/1.7
*PLEASE PROVIDE SHOP DRAWINGS AND SPECIAL INSP. REPORT FOR GUNITE FOUNDATION SYSTEM.