Permit: T05CM05105

Parcel: 117065960


Addresses:

467 S 3RD AV

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
05/08/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
INSTALL A SWEEP ON KIT TRAP ARM
"HORIZONTAL CHANGES OF DIRECTION SHALL BE MADE W/WYE PATTERN FITTINGS."
05/03/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
- CONDENSATE MAY DRAIN TO STANDPIPE FOR WASHER.
RETEST AFTER INSTALLING SANTEE.
- PIPING TO SOLAR HEATER IS NOT UNDER TEST.
- SEC. 1004 UPC - "THE TRAP SHALL BE THE SAME SIZE AS THE TRAP ARM TO WHICH IT IS CONNECTED". YOU CANNOT REDUCE A TRAP ARM IN THE RUN.
- PLAN SPECIFIES TYPE L COPPER. SOME M HAS BEEN USED.
- INSTALLATION STANDARD IS 5 REQUIRES CLOSET FLANGES TO BE SECURELY FASTENED TO FLOOR. ALSO SUPPORT LAUNDRY TRAP ARM.
- FHA SHOWER DRAINS NOT YET INSTALLED SHOWER PAN LINER SHALL BE WATER TESTED.
- TUB NOT YET INSTALLED.