Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/08/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* INSTALL A SWEEP ON KIT TRAP ARM "HORIZONTAL CHANGES OF DIRECTION SHALL BE MADE W/WYE PATTERN FITTINGS." |
|
| 05/03/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* - CONDENSATE MAY DRAIN TO STANDPIPE FOR WASHER. RETEST AFTER INSTALLING SANTEE. - PIPING TO SOLAR HEATER IS NOT UNDER TEST. - SEC. 1004 UPC - "THE TRAP SHALL BE THE SAME SIZE AS THE TRAP ARM TO WHICH IT IS CONNECTED". YOU CANNOT REDUCE A TRAP ARM IN THE RUN. - PLAN SPECIFIES TYPE L COPPER. SOME M HAS BEEN USED. - INSTALLATION STANDARD IS 5 REQUIRES CLOSET FLANGES TO BE SECURELY FASTENED TO FLOOR. ALSO SUPPORT LAUNDRY TRAP ARM. - FHA SHOWER DRAINS NOT YET INSTALLED SHOWER PAN LINER SHALL BE WATER TESTED. - TUB NOT YET INSTALLED. |