Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/08/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/03/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ALL CABLING INSTALLED INSIDE STUD CHANNEL MUST BE 1 1/4" MIN. FROM STUD SIDES TO PREVENT SCREWS/NAIL PUNCTURE. 2. LB FITTING IN GARAGE REQUIRE APPROVED CONNECTORS FOR ROMEX. 3. VERIFY WATER PIPE BONDING. |