Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T05CM05097
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/17/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 02/13/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE OPEN FRONT TOILET SEATS INSTALL EXPANSION TANK BETWEEN WH AND SHUT OFF VALVE INSTALL CLEANOUTS AT HAND SINKS PROPER CLEAN OUT PLUGS REQUIRED FOR EXCEPTING COVER SCREWS (DRILLING ABS NOT ACCEPTED) PROPER DRAINAGE FITTING REQUIRED FOR VENT AT AAV LOCATION (A SANTEE ON ITS BACK IS NOT AN APPROVED DRAINAGE FITTING) WASH & RINSE COMPARTMENTS OF 3 COMP SINK SHOULD PIPE DIRECTLY SANITIZE COMPARTMENT SHALL DRAIN THROUGH AN AIR GAP |