Permit: T05CM05097

Parcel: 106090530

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM05097

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/21/2006 ELECTRIC - FINAL Approved
02/17/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/13/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio BOND SERVICE RACEWAYS
SAME SIZE CONDUCTORS ONLY UNDER TERMINATIONS
IDENTIFY BRANCH CKTS AND SERVICE DISCONNECTS
BOND WATER AND GAS TO SERVICE
REMOVE OLD MAST
FINISH CORRECTIONS FROM PREVIOUS INSPECTION
PAY RE INSPECTION FEE
02/08/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*REPLACE DEVICES THAT HAVE BEEN PAINTED OVER
INSTALL ALL DEVICE COVERS AND MAKE SURE DEVICES ARE NOT LOOSE AND SIT FLUSH TO WALL
IDENTIFY BRANCH CKT'S IN PANEL DIRECTORY'S
HAVE ELECTRICIAN ON SITE TO PROVIDE ACCESS TO PANELS AND METER INSPECTION