Permit: T05CM05097

Parcel: 106090530

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T05CM05097

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
02/21/2006 ELECTRIC - SERVICE UPGRADE Approved
12/22/2005 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*SERVICE OK TO BE ENERGIZED FOR THE PURPOSE OF CHANGE OVER. CALL FOR COMPLETE SERVICE AND BRANCH CKT INSPECTION WHEN COMPLETE
12/20/2005 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :$
12:00 PM STRUCTURE LOCKED, NOBODY ON JOB SITE
12/14/2005 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTES:
1. NEUTRAL TO BE BONDED AT PANEL PER 250.24 NEC 250.28
2. EXPOSE METAL CONDUIT AT END BELOW GROUND FOR INSPECTION WHERE GROUND ELECTRODES CONDUCTOR EXITS TO GROUND RODS. INSTALL BOND BUSHING & BOND CONDUIT TO #2 BARE PER 250 NEC.
3. VERIFY WATER & GAS PIPE BONDING
4. ONE LINE DIA. SHOW BOTH PANELS FED FROM METAL SOCKET?
5. SECURE CABLING ENTERING CONDUIT SLEEVE IN CEILING (TO SERVICE)