Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T05CM05097
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/21/2006 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 12/22/2005 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :*SERVICE OK TO BE ENERGIZED FOR THE PURPOSE OF CHANGE OVER. CALL FOR COMPLETE SERVICE AND BRANCH CKT INSPECTION WHEN COMPLETE | |
| 12/20/2005 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :$ 12:00 PM STRUCTURE LOCKED, NOBODY ON JOB SITE |
|
| 12/14/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES: 1. NEUTRAL TO BE BONDED AT PANEL PER 250.24 NEC 250.28 2. EXPOSE METAL CONDUIT AT END BELOW GROUND FOR INSPECTION WHERE GROUND ELECTRODES CONDUCTOR EXITS TO GROUND RODS. INSTALL BOND BUSHING & BOND CONDUIT TO #2 BARE PER 250 NEC. 3. VERIFY WATER & GAS PIPE BONDING 4. ONE LINE DIA. SHOW BOTH PANELS FED FROM METAL SOCKET? 5. SECURE CABLING ENTERING CONDUIT SLEEVE IN CEILING (TO SERVICE) |