Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T05CM05097
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/21/2006 | ELECTRIC - INTERMEDIATE | Approved | ||
| 01/10/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection : OK TO COVER ELECTRICAL WALLS ONLY BOTH BATHS, LAUNDRY & KITCHEN | |
| 01/06/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) STILL HAVE ROMEX IN CEILING 2) ROMEX NEED PROPER CONNECTOR ENTERING J-BOXES 3) J-BOXES NEED TO BE GROUNDED 4) ALL MC NEEDS TO BE PROPERLY SECURED AND SUPPORTED |
|
| 01/04/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) NEC 334.12 (A) DOES NOT ALLOW ROMEX IN A COMMERCIAL SUSPENDED CEILING 2) SUPPORT FIRE ALARM CONDUCTORS PROPERLY IN CEILING |