Permit: T05CM05097

Parcel: 106090530

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T05CM05097

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/21/2006 ELECTRIC - INTERMEDIATE Approved
01/10/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection : OK TO COVER ELECTRICAL WALLS ONLY BOTH BATHS, LAUNDRY & KITCHEN
01/06/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) STILL HAVE ROMEX IN CEILING
2) ROMEX NEED PROPER CONNECTOR ENTERING J-BOXES
3) J-BOXES NEED TO BE GROUNDED
4) ALL MC NEEDS TO BE PROPERLY SECURED AND SUPPORTED
01/04/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) NEC 334.12 (A) DOES NOT ALLOW ROMEX IN A COMMERCIAL SUSPENDED CEILING
2) SUPPORT FIRE ALARM CONDUCTORS PROPERLY IN CEILING