Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T05CM05090
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/20/2006 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
03/16/2006 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONNECT ALL GROUNDS IN PANEL 2) MULTI GROUND WIRES MUST BE ALL SAME WIRE GAUGE ON SAME LUG 3) DBL LUGGING OF NEUTRAL WIRES NOT ALLOWED 4) ANTI SIPHON VALVE MUST BE NON REMOVABLE 5) NEED POST TENSION CERT |