Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/05/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 02/03/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSTALL PEX PER MANUFACTURERS INSTALLATION STANDARDS ALLOW FOR EXPANSION. USE OF UPC APPROVED - LISTED FITTINGS REQUIRED SEE CLOSET FLANGE AND 8" COUPLING. PROVIDE TEST ON SHOWER RISER & TUB TO FLOOD RIM USE OF PROPER DRAINAGE FITTINGS REQUIRED ON HORIZONTAL CHANGE OF DIRECTIONS INTERMEMBERING OF DISSIMILAR MATERIALS IS PROHIBITED INSTALL BRASS NIPPLES FOR HBS AND SECURE DROP CORRECT KINK IN PEX AT WASHER BOX |