Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/28/2005 | FRAMING | Approved | IVRS - Inspection :* | |
| 12/23/2005 | FRAMING | Partial Approval | IVRS - Inspection :* 1) CORRECT SPACING HIP TRUSSES IN GARAGE 2) SUPPLY OK 3) NO DWV TEST 4) REROUTE A/C SECONDARY DRAIN TO OBVIOUS LOCATION 5) OK TO INSULATE EXCEPT WHERE ABS PIPES LOCATED 6) INSURE ISLAND WALL IS PLUMB AFTER SHEETROCK REMOVED |
|
| 12/22/2005 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
| 12/16/2005 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) SHEARWALL 8 REQUIRES EDGE NAILING AT 4" ON CENTER 2) SHEARWALL 8 NOT CONNECTED TO TRUSSES PER 6/SD3 3) LATH AND FRAME BARRIER NOT DONE AT REAR 4) NO DWV WATER TEST 5) NO POTABLE WATER TEST 6) DRYER MUST EXHAUST OUTSIDE OF ATTIC 7) STOPPED INSPECTION-HOUSE NOT COMPLETE ENOUGH TO INSPECT |