Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM05044
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/18/2009 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/17/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* COMPLETE PREVIOUS INSPECTION ITEM |
|
06/16/2009 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* RECEPTACLES ON SOUTH WALL WHEN TESTED INDICATE HAVE NO EQUIPMENT GROUND |
|
06/11/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. RECEPTS SOUTH WALL HAVE NO POWER 2. VERIFY EM/EXITS ARE WORKING 3. RECALL WHEN READY |
|
05/20/2009 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. VERIFY GROUNDING ELECTRODE SYSTEM FOR SERVICE 2. VERIFY BONDING OF METAL PIPING SYSTEMS 3. HAVE SEVERAL NON-CODE COMPLIANT TAPS OFF OF SERVICE DISCONNECT NEED TO BE REMOVED AND SERVICE CLEANED UP 4. ADDRESS UNITS TO METERS & DISCONNECTS 5. MARK "SERVICE DISCONNECTS" 6. SERVICE SHOULD BE UPGRADED DUE TO ALL ENCLOSURES AND RACEWAYS NENA1 - DO NOT HAVE PROPER WORKING CLEARANCES BECAUSE OF GAS PIPING AND METERS 7. POWER TO BE ON TO GET FINAL |