Permit: T05CM05044

Parcel: 131050010


Addresses:

1906 S CRAYCROFT RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/18/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/17/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
COMPLETE PREVIOUS INSPECTION ITEM
06/16/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
RECEPTACLES ON SOUTH WALL WHEN TESTED
INDICATE HAVE NO EQUIPMENT GROUND
06/11/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. RECEPTS SOUTH WALL HAVE NO POWER
2. VERIFY EM/EXITS ARE WORKING
3. RECALL WHEN READY
05/20/2009 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. VERIFY GROUNDING ELECTRODE SYSTEM FOR SERVICE
2. VERIFY BONDING OF METAL PIPING SYSTEMS
3. HAVE SEVERAL NON-CODE COMPLIANT TAPS OFF OF SERVICE DISCONNECT NEED TO BE REMOVED AND SERVICE CLEANED UP
4. ADDRESS UNITS TO METERS & DISCONNECTS
5. MARK "SERVICE DISCONNECTS"
6. SERVICE SHOULD BE UPGRADED DUE TO ALL ENCLOSURES AND RACEWAYS NENA1 - DO NOT HAVE PROPER WORKING CLEARANCES BECAUSE OF GAS PIPING AND METERS
7. POWER TO BE ON TO GET FINAL