Permit: T05CM05044

Parcel: 131050010


Addresses:

1906 S CRAYCROFT RD


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T05CM05044

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
06/18/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/16/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/08/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) INSTALL 60 AMP FUSES AT SERVICE
2) RECALL FOR FINAL AFTER POWER IS ON
04/16/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK SURFACE MOUNTED LIGHTS
01/21/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK WALLS
2. OK HARD LID RESTROOM
01/16/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED MIN. 4" SQUARE OUTLET BOXES PER PLAN
BOXES OVERFILLED
2. NEED TO GROUND ALL METAL BOXES
3. USE CONNECTORS LISTED FOR USE WITH MC CABLES
4. BLANK OPEN KNOCKOUTS
5. ALL BOXES TO BE ACCESSIBLE
6. RECALL WHEN READY
05/08/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*