Permit: T05CM05032

Parcel: 122092150


Addresses:

4005 E JUSTIN LN

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
07/25/2006 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
03/01/2006 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) EXCEPT PORCH CORBEL DETAIL 10/5
02/28/2006 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
1) CANCELLED BY SUPER
02/27/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLY WITH DETAIL 1/5 80 AT 6" ON CENTER AT TRUSS BLOCKING
2) REFEE
02/22/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLY WITH NOTE 4 FROM PREVIOUS INSPECTION
2) COMPLY WITH NOTE 5
3) COMPLY WITH NOTE 7 & 8
02/14/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLY WITH PREVIOUS INSPECTION
02/13/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) TO MUCH DEBRIS ON ROOF
2) PROVIDE 18" GAP ALL OSB ENDS AND JOINTS
3) PER TRUSS CALCS DBL TOP PLATES REQUIRED AT MID BEARING C1 AND C2 TRUSSES FOR 3 POINT BEARING TRUSSES
4) PER DETAIL 1/5 NAIL 2 X 8 BLOCKS 6" ON CENTER THROUGHOUT
5) INSTALL H2.5 EACH STUD PER DETAIL 12/5
6) NAIL ALL JOINTS 1/5 EAST WALL 6" ON CENTER AND SOUTH WALL
7) DETAIL 10/5 CENTER POST LAG BOLT INTO CORBEL ?
8) INSTALL H2.5 PER DETAIL 8/5
02/09/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GATES LOCKED-UNABLE TO ENTER