Inspection History Details
Inspection Status: Approved
Inspection History: REINFORCED MASONRY PRE-GROUT
Permit Number - T05CM05027
Inspection Description - REINFORCED MASONRY PRE-GROUT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/04/2008 | REINFORCED MASONRY PRE-GROUT | Approved | FINAL INSPECTION NOT DONE BY COT. APPROVED PER REVIEW OF SPECIAL INSPECTION REPORTS. | |
| 09/26/2007 | REINFORCED MASONRY PRE-GROUT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/12/2007 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* WEST WALL 9'4" A.F.F.E SOUTH WALL 9'4" A.F.F.E EXCEPT FOR JAMBS AND LINTEL |
|
| 02/05/2007 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) NOTE: EXTERIOR WALL 8" X 8" X 16" MASONRY WALL FOR BLDG #6 DETAIL 1 ON SHEET A6 FIRST LIFT 4'-8" 2) NEXT INSPECTION PROVIDE REPORTS FOR STEM WALL CORRECTION LEFT ON 01/29/07 3) MUST CALL FOR INSPECTION PRIOR TO COVERING OR CONCEALING WORK |
|
| 01/29/2007 | REINFORCED MASONRY PRE-GROUT | Denied | IVRS - Inspection : See detailed listing on site.| 999* VERTICAL REBAR ON CONTROL JOINT ( 2 #4 EA. SIDE) NEED TO BE FROM FOOTING (THEN CONT. OVERLAP 30" MIN. WITH #5 EA. SIDE OF C.J ON WALL) * PROVIDE SPECIAL INSPECTION REPORT FOR EPOXY CONNECTIONS AT THE TIME OF REINSPECTION. AND REQ. INSPECTION 01010 STEM WALL |