Inspection History Details
Inspection Status: Not Applicable
Inspection History: REINFORCED MASONRY PRE-GROUT
Permit Number - T05CM05026
Inspection Description - REINFORCED MASONRY PRE-GROUT
Inspection Status - Not Applicable
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/20/2008 | REINFORCED MASONRY PRE-GROUT | Not Applicable | ||
| 02/12/2007 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* GRIDLINE OR EAST WALL 9'4" A.F.F.E SOUTH WALL 9'4" A.F.F.E EXCEPT FOR JAMB AND LINTEL |
|
| 02/05/2007 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* 1) NOTE: EXTERIOR WALL 8" X 8" X 16" MASONRY WALL FOR BLDG #5 DETAIL 1 ON SHEET A6 FIRST LIFT 4'-8" 2) NEXT INSPECTION PROVIDE REPORTS FOR STEM WALL CORRECTION LEFT ON 01/29/07 3) MUST CALL FOR INSPECTION PRIOR TO COVERING OR CONCEALING WORK |
|
| 01/29/2007 | REINFORCED MASONRY PRE-GROUT | Denied | IVRS - Inspection : See detailed listing on site.| 999* VERTICAL REBAR ON CONTROL JOINT 2 #4 EACH SIDE NEED TO BE FROM FOOTING (THEN CONT. OVERLAP 30" WITH #5 EACH SIDE OF IN WALL) PROVIDE SPECIAL INSPECTION ON EPOXY CONNECTIONS (REPORT OF INSPECTION AT THE TIME OF REINSPECTION) |