Permit: T05CM05023

Parcel: 110061550

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
12/06/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*
APARTMENTS APPEAR OCCUPIED - APARTMENTS LOCKED, NO ONE AROUND -- SORRY I COULDN'T SIGN YOUR PERMIT CARD.
12/02/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*A/C UNITS ARE OVERFUSED AT 30 AMP.
25 AMP IS MAX FUSE SIZE.
12/01/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LOW VOLTAGE WIRING MUST BE PROTECTED FROM DAMAGE-USE CONDUIT
2) PAINT EXPOSED PVC WITH LATEX PAINT
3) BLOCK AND CLAMP DRAIN LINES
4) MARK UNIT DATA PLATES WITH PROPER HEAT STRIP INSTALLED-FUSE ACCORDINGLY
5) A/C UNITS ARE NOT LEVEL
6) RECALL FOR FINAL